AJD 28-6
Product: JOHN DEERE
Alternator: PI 144 G - 60Hz
Control System: DSE 6020
Certificate
General Characteristics
3 Phase, 60 Hz, PF 0.8
ENGINE SPECIFICATIONS
ALTERNATOR SPECIFICATIONS
SIZE and WEIGHT
TS ISO 8528
CE
SZUTEST
2000/14/EC
Model Name |
AJD 28-6 |
||
---|---|---|---|
Frequency (Hz) |
60 |
||
Fuel Type |
Diesel |
||
Engine Made and Model |
JOHN DEERE - 3029 DF 128 - 60Hz |
||
Alternator Made and Model |
Stamford - PI 144 G - 60Hz |
||
Control Panel Model |
DSE 6020 |
||
Canopy | AK 20 |
Voltage | STANDBY RATING (ESP) | PRIME RATING (PRP) | Standby Amper | ||
---|---|---|---|---|---|
kVA | kW | kVA | kW | ||
480/277 | 35 | 28.00 | 31.25 | 25.00 | 42.10 |
380/220 | 33.75 | 27.00 | 30 | 24.00 | 51.28 |
208/120 | 35 | 28.00 | 30 | 24.00 | 97.15 |
STANDBY RATING (ESP) : Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. ESP is in accordance with ISO 8528-1. Overload is not allowed.
PRIME RATING (PRP) : Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528-1. 10 % overload capability is available for a period of 1 hour within 12-hour perod of operation.
PRIME RATING (PRP) : Applicable for supplying power to varying electrical load for unlimited hours. PRP is in accordance with ISO 8528-1. 10 % overload capability is available for a period of 1 hour within 12-hour perod of operation.
Engine |
JOHN DEERE |
||
---|---|---|---|
Engine Model | 3029 DF 128 - 60Hz | ||
NO. OF CYLINDERS AND BUILD | 3 cylinders - in line | ||
BORE AND STROKE | mm | 106 X 110 | |
TOTAL DISPLACEMENT | L | 2.9 | |
Aspiration | Naturally Aspirated | ||
COMPRESSION RATIO | 17.2:1 | ||
RATED SPEED (RPM) | d/dk | 1800 | |
OIL CAPACITY | L | 5 | |
Standby Power (kW/HP) | 40/53.6 | ||
Block Heater QTY | |||
1 | |||
Block Heater Power (Watt) | 500 | ||
Fuel Type | |||
Diesel | |||
Injection Type and System | |||
Direct | |||
Type of Fuel Pump | |||
Stanadyne DB2 Rotary Type | |||
Governor System | |||
Mechanic | |||
Operating Voltage (Vdc) | |||
12 Vdc | |||
Battery and Capacity (Qty/Ah) | 1x55 | ||
Cooling Method | |||
Water Cooled | |||
Coolant Capacity (engine only / with radiator) (lt) | 5.7/15.50 | ||
Air Filter | |||
Dry Type | |||
Fuel Cons. Prime With %100 Load (lt/hr) | 7.9 | ||
Fuel Cons. Prime With %75 Load (lt/hr) | 6.35 | ||
Fuel Cons. Prime With %50 Load (lt/hr) | 4.47 |
Manufacturer | Stamford | |
---|---|---|
Alternator Made and Model | PI 144 G - 60Hz | |
Frequency (Hz) | Hz | 60 |
Power (kVA) | kVA | 30 |
Design | 4 Pole, Brushless | |
Voltage | V | 380 |
Phase | 3 | |
A.V.R. | AS480 | |
Voltage Regulation | (+/-) | 1 |
Insulation System | H | |
Rated Power Factor | 0.8 | |
WEIGHT COMP. GENERATOR (Kg) | 160 | |
COOLING AIR (m³/min) | m3 | 7,3 |
Open Type | DRY WEIGHT (kg.) (kg.) |
LENGTH (mm.) |
WIDTH (mm.) |
HEIGHT (mm.) |
TANK CAPACITY (lt.) (Lt.) |
---|---|---|---|---|---|
720 | 1490 | 900 | 1123 | 70 | |
CANOPY | DRY WEIGHT (kg.) (kg.) |
LENGTH (mm.) |
WIDTH (mm.) |
HEIGHT (mm.) |
TANK CAPACITY (lt.) (Lt.) |
AK 20 |
900 | 2101 | 956 | 1482 | 70 |
Control System: DSE 6020
1. Main status display.
2. Display scroll button.
3. Page(information) button.
4. Common alarm indicator.
5. Status LED's.
6. Operation selecting buttons.
2. Display scroll button.
3. Page(information) button.
4. Common alarm indicator.
5. Status LED's.
6. Operation selecting buttons.
Devices
●DSE, model 6020 Auto Mains Failure control module.
●Battery charger input 198-264 volt, output 27,6 V 5 A (24 V) or 13,8 Volt 5A (12V)
●Emergency stop push button and fuses for control circuits.
CONSTRUCTION and FINISH
●Battery charger input 198-264 volt, output 27,6 V 5 A (24 V) or 13,8 Volt 5A (12V)
●Emergency stop push button and fuses for control circuits.
●Components installed in sheet steel enclosure. Phosphate chemical, pre-coating of steel provides corrosion resistant surface. Polyester composite powder topcoat forms high gloss and extremely durable finish. Lockable and hinged panel door provides easy access to components.
INSTALLATION
Control panel is mounted on baseframe with steel stand. Located at the right side of the generator set (When you look at the Gen.Set. from Alternator)
GENERATING SET CONTROL UNIT
The DSE 6020 is a standard control module for our generator sets up to 200kVA and ıt has been designed to start and stop diesel and gas generator sets.
The DSE 6020 module has been designed to monitor generator frequency, volt, current, engine oil pressure, coolant temperature running hours and battery volts.
Module monitors the mains supply and switch over to the generator when the mains power fails.
The DSE6020 also indicates operational status and fault conditions, Automatically shutting down the Gen. Set and giving true first up fault condition of Gen. Set failure.The LCD display indicates the fault.
STANDARD SPECIFICATIONS
●Microprocessor controlled.
●LCD display makes information easy to read.
●4-line, 64 x 132 pixel display.
●Automatically transfers between mains (utilty) and generator power.
●Manual programming on front panel.
●User-friendly set-up and button layout.
●Remote start.
●Event logging (5)showing date and time.
●Controls: Stop/Reset, Manual, Auto, Test, Start, buttons. An additional push button next to the LCD display is used to scroll through the modules' metering displays.
STATIC BATTERY CHARGER
The DSE 6020 module has been designed to monitor generator frequency, volt, current, engine oil pressure, coolant temperature running hours and battery volts.
Module monitors the mains supply and switch over to the generator when the mains power fails.
The DSE6020 also indicates operational status and fault conditions, Automatically shutting down the Gen. Set and giving true first up fault condition of Gen. Set failure.The LCD display indicates the fault.
STANDARD SPECIFICATIONS
●Microprocessor controlled.
●LCD display makes information easy to read.
●4-line, 64 x 132 pixel display.
●Automatically transfers between mains (utilty) and generator power.
●Manual programming on front panel.
●User-friendly set-up and button layout.
●Remote start.
●Event logging (5)showing date and time.
●Controls: Stop/Reset, Manual, Auto, Test, Start, buttons. An additional push button next to the LCD display is used to scroll through the modules' metering displays.
Instruments
ENGINE
●Engine speed.
●Oil pressure.
●Coolant temperature.
●Run time.
●Battery volts.
●Configurable timing.
GENERATOR
●Voltage (L-L, L-N).
●Current (L1-L2-L3).
●Frequency.
MAINS
●Voltage (L-L, L-N).
●Frequency.
●Mains ready.
●Mains enabled.
●Gen. Set ready.
●Gen. Set enabled.
ENGINE
●Engine speed.
●Oil pressure.
●Coolant temperature.
●Run time.
●Battery volts.
●Configurable timing.
GENERATOR
●Voltage (L-L, L-N).
●Current (L1-L2-L3).
●Frequency.
MAINS
●Voltage (L-L, L-N).
●Frequency.
●Mains ready.
●Mains enabled.
●Gen. Set ready.
●Gen. Set enabled.
Protection Circuits
WARNING
●Charge failure.
●Battery Low/High voltage.
●Fail to stop.
●Low /High generator voltage.
●Under/over generator frequency.
●Over /Under speed.
●Low oil pressure.
●High coolant temperature.
SHUT DOWNS
●Fail to start. ●Emergency stop.
●Low oil pressure.
●High coolant temperature.
●Over /Under speed.
●Under/over generator frequency.
●Under/over generator voltage.
●Oil pressure sensor open.
●Coolant temperature sensor open.
ELECTRICAL TRIP
●Generator over current.
WARNING
●Charge failure.
●Battery Low/High voltage.
●Fail to stop.
●Low /High generator voltage.
●Under/over generator frequency.
●Over /Under speed.
●Low oil pressure.
●High coolant temperature.
SHUT DOWNS
●Fail to start. ●Emergency stop.
●Low oil pressure.
●High coolant temperature.
●Over /Under speed.
●Under/over generator frequency.
●Under/over generator voltage.
●Oil pressure sensor open.
●Coolant temperature sensor open.
ELECTRICAL TRIP
●Generator over current.
Options
●Flexible sensor can be controlled with temperature, pressure, percentage (warning/shutdown/electrical trip)
●Local setting parameters and monitoring from PC to control module with USB connection (max 6 mt).
●Flexible sensor can be controlled with temperature, pressure, percentage (warning/shutdown/electrical trip)
●Local setting parameters and monitoring from PC to control module with USB connection (max 6 mt).
Standards
Elecrical Safety / EMC compatibility
●BS EN 60950 Electrical business equipment.
●BS EN 61000-6-2 EMC immunity standard.
●BS EN 61000-6-4 EMC emission standard
Elecrical Safety / EMC compatibility
●BS EN 60950 Electrical business equipment.
●BS EN 61000-6-2 EMC immunity standard.
●BS EN 61000-6-4 EMC emission standard
● Battery charger is manufactured with switching-mode and SMD technology and ıt has high efficiency.
Battery charger models' output V-I characteristic is very close to square and output is 5 amper, 13,8 V for 12 volt and 27,6 V for 24 V . Input 198 - 264 volt AC.
Proline 2405 has fully output shot circuit protection and ıt can be used as a current source.
Proline 1205/2405 charger has high efficiency, long life, low failure rate, light weight and low heat radiated in accordance with linear alternatives.
The charger is fitted with a protection diode across the output.
Connect charge fail relay coil between positive output and CF output.
They are equipped with RFI filter to reduce electrical noise radiated from the device.
Galvanically isolated input and output typically 4kV for high reliability.
Battery charger models' output V-I characteristic is very close to square and output is 5 amper, 13,8 V for 12 volt and 27,6 V for 24 V . Input 198 - 264 volt AC.
Proline 2405 has fully output shot circuit protection and ıt can be used as a current source.
Proline 1205/2405 charger has high efficiency, long life, low failure rate, light weight and low heat radiated in accordance with linear alternatives.
The charger is fitted with a protection diode across the output.
Connect charge fail relay coil between positive output and CF output.
They are equipped with RFI filter to reduce electrical noise radiated from the device.
Galvanically isolated input and output typically 4kV for high reliability.
Canopy: AK 20
1. Steel structures
2. Emergency stop push button
3. Control panel is right side of the set.
4. Corrosion.resistant locks and hinges
5. Sump drains valves
6. Sound proof foam metarial
7. Base frame .tank
2. Emergency stop push button
3. Control panel is right side of the set.
4. Corrosion.resistant locks and hinges
5. Sump drains valves
6. Sound proof foam metarial
7. Base frame .tank
INTRODUCTION
Sound–attenuated and Weather-protective Enclosures Sound-attenuated and weather protective enclosures for generating sets from Aksa, meet event the sound requirements and provide optimum protection from inclement weather and development by our specialist acoustic engineers. Our modular designed sound insulated canopies provide ease of access for servicing and general maintenance and interchangeable components permitting on-site repair. Enclosures are designed to optimize genset cooling performance, providing you with confidence that genset ratings and ambient capability.
STANDARD SPECIFICATIONS
Compact footprint, low profile design.
Enclosure, generator set, exhaust system and fuel tank are pre-ssembled, pre-integrated and shipped as one package
Body made from steel components treated with polyester powder coating
Fire retardant foam insulation
Easy access to all service points
Exhaust system inside canopy
Large doors on each side
Control panel viewing window in a lockable access door
Emergency stop push button mounted on enclosure exterior
Cooling fan and battery charging alternator fully guarded
Fuel fill and battery can only be reached via lockable access doors.
Lifting points on the top of canopy and base frame
Customer options available to meet your applications needs.
Aksa makes its generating sets' noise level tests in accordance with directive 2000/14/EC validation of the noise level test has been aproved by the notified body Szutest
Enclosure, generator set, exhaust system and fuel tank are pre-ssembled, pre-integrated and shipped as one package
Body made from steel components treated with polyester powder coating
Fire retardant foam insulation
Easy access to all service points
Exhaust system inside canopy
Large doors on each side
Control panel viewing window in a lockable access door
Emergency stop push button mounted on enclosure exterior
Cooling fan and battery charging alternator fully guarded
Fuel fill and battery can only be reached via lockable access doors.
Lifting points on the top of canopy and base frame
Customer options available to meet your applications needs.
Aksa makes its generating sets' noise level tests in accordance with directive 2000/14/EC validation of the noise level test has been aproved by the notified body Szutest
CANOPY MODEL | AK 20 | |
---|---|---|
WIDTH | mm. | 956 |
LENGTH | mm. | 2101 |
HEIGHT | mm. | 1482 |
TANK CAPACITY (lt.) | Lt. | 70 |